rail mounting device, 2 rail units
Project design and commissioning with ETS5 or a more recent version
Intended use
Connection between KNX devices and PC or other data processing devices via IP
Operation as data interface
Mounting on DIN rail according to EN 60715 in distribution box
Product characteristics
KNX Data Secure compatible with ETS 5.7.3 or higher
KNX IP Secure compatible with ETS 5.7.3 or higher
Max. 48 telegrams per second in IP secure mode
LED display for KNX communication, Ethernet communication and programming mode
Configuration via ETS, Telnet or software tool
SNTP server, buffered
Commissioning with display support
Max. 8 connections to IP terminal devices, e.g. for simultaneous visualisation and configuration
Outage message of the KNX system to the IP system
Electrical isolation between KNX and IP network
Power consumption max. 1 W
V05 or higher and in combination with remote access licence (ref.-no. IPS-L):
Encrypted access to KNX devices for configuration and maintenance outside the local network
Enabling access via communication objects
Feedback on access and programming processes via communication objects
Requirements for administered networks
TCP port 3672 for the IP device
TCP port 3671 for the PC with ETS
DNS address 9.9.9.9 with static network (for NTP server)
Remote host access: ipsremote.jung.de
Technical data about IP interface, Rail mounting device, 2 rail units, Secure IPS 300 SREG